Transformer Turns Ratio Calculator
Calculate a transformer's turns ratio from winding turns, rated voltages, or impedances to be matched, and get the secondary voltage, primary current, VA, and impedance ratio of an ideal transformer.
Enter primary and secondary turns for the turns ratio; add primary voltage and secondary current to also get secondary voltage, primary current, and apparent power.
Results
Enter the two values needed for the selected mode to see the turns ratio.
Usage examples
Secondary voltage and current from the turns
For a transformer with 500 primary and 50 secondary turns, 120 V in and a 2 A load, enter 500, 50, 120, and 2 under 'From turns'. You get a 10 : 1 turns ratio, 12 V on the secondary, 0.2 A on the primary, 24 VA, and a 100 : 1 impedance ratio.
Choosing secondary turns for a 230 V to 12 V transformer
Under 'From voltages', enter 230 V primary and 12 V secondary: the turns ratio is about 19.167 : 1. With a 1,150-turn primary, the secondary needs 60 turns. In practice the secondary is often wound with a few extra turns to make up for voltage drop under load.
Matching a tube amp output transformer
Under 'Impedance matching', enter 8,000 Ω on the primary and an 8 Ω speaker on the secondary. The impedance ratio is 1000 : 1 and the required turns ratio is √1000 ≈ 31.62 : 1. With a 2,000-turn primary, the secondary works out to about 63.2 turns, so roughly 63.
A 120 V to 240 V step-up transformer
Enter 120 V primary and 240 V secondary under 'From voltages' and it shows a 1 : 2 step-up transformer. With 5 A on the secondary, the primary draws 10 A, which shows that doubling the voltage at the same power halves the current.
Comparing a TTR test result with the nameplate
For a 480 V/120 V nameplate, entering 480 and 120 under 'From voltages' gives 4 : 1. If your TTR tester reads 4.012, the deviation is (4.012 − 4) ÷ 4 = 0.3%, which you can then check against the tolerance in the test standard you work to.
Quick reference
Ideal turns ratio for common voltage pairs
| Primary | Secondary | Turns ratio Np : Ns | Impedance ratio | Type |
|---|---|---|---|---|
| 120 V | 240 V | 1 : 2 | 0.25 : 1 | Step-up |
| 240 V | 120 V | 2 : 1 | 4 : 1 | Step-down |
| 480 V | 240 V | 2 : 1 | 4 : 1 | Step-down |
| 480 V | 120 V | 4 : 1 | 16 : 1 | Step-down |
| 600 V | 120 V | 5 : 1 | 25 : 1 | Step-down |
| 120 V | 24 V | 5 : 1 | 25 : 1 | Step-down |
| 120 V | 12 V | 10 : 1 | 100 : 1 | Step-down |
| 230 V | 110 V | 2.091 : 1 | 4.372 : 1 | Step-down |
| 230 V | 24 V | 9.583 : 1 | 91.84 : 1 | Step-down |
| 230 V | 12 V | 19.167 : 1 | 367.361 : 1 | Step-down |
| 7,200 V | 240 V | 30 : 1 | 900 : 1 | Step-down |
Frequently asked questions
How is the turns ratio calculated?
Turns ratio a = Np ÷ Ns. In an ideal transformer the voltage ratio equals the turns ratio (Vp ÷ Vs = a), the current ratio is its inverse (Ip ÷ Is = 1 ÷ a), and the impedance ratio is its square (Zp ÷ Zs = a²). For example, 500 : 50 turns gives a = 10, stepping 120 V down to 12 V.
Is a turns ratio above 1 step-down or step-up?
This calculator defines a = Np/Ns, so a > 1 is step-down (lower secondary voltage), a < 1 is step-up, and a = 1 is a 1:1 isolation transformer. Some references define the ratio as Ns/Np instead, so check which convention a source uses.
Why is my measured secondary voltage higher than calculated?
A transformer's nameplate secondary voltage is normally specified at rated load. Winding resistance and leakage reactance make the voltage drop under load, so manufacturers wind a few extra secondary turns to compensate. Measured with no load, the voltage is therefore higher than the nameplate, and the gap is larger on small transformers.
Why is the impedance ratio the square of the turns ratio?
Voltage scales by a and current by 1/a, so impedance Z = V ÷ I scales by a × a = a². To make an 8 Ω speaker look like 8 kΩ you need an impedance ratio of 1000, which means a turns ratio of its square root, about 31.6.
How do I find the primary current?
In an ideal transformer input power equals output power, so Ip = Is ÷ a. With 2 A on the secondary and a turns ratio of 10, the primary current is 0.2 A. A real transformer draws a little more because of magnetizing current and losses.
Does this work for three-phase transformers?
The same equation gives the turns ratio of each phase winding. But with mixed connections such as delta-wye, the line-to-line voltage ratio differs from the winding turns ratio by a factor of √3, so take the connection into account when working from line voltages.
Does a turns ratio apply to DC?
No. A transformer induces voltage through a changing magnetic flux, so it only works on AC. Applying DC induces nothing on the secondary, and the primary current is limited only by winding resistance, which can be dangerous.