Fan Laws Calculator
Calculate how airflow (CFM), static pressure, and power change with fan speed using the fan laws, including RPM-to-RPM scaling for VFD adjustments. Free online tool for predicting energy savings from slowing a fan, checking motor limits, or matching airflow after a filter change, computed instantly.
Result
Speed
1,500
Airflow
3,000
Pressure
2.25
Power
1.688
Usage examples
Predicting airflow after changing fan speed with a VFD
If you know the current speed and airflow, see exactly how airflow changes when you adjust speed with a variable frequency drive.
Estimating speed and power needed for a target airflow
Set your desired airflow first, and back-calculate the speed ratio and resulting power change needed to reach it.
Seeing how speed changes affect power draw
Since power scales with the cube of speed, see how much even a small speed change affects power consumption.
Slowing a supply fan to cut energy use during off-peak hours
Starting from 1200 RPM, 4000 CFM, and 1.2 in. w.g., solve for a target of 900 RPM to see the resulting drop in airflow, static pressure, and motor power during low-demand periods.
Checking if a motor can handle a speed increase
From a known point of 1750 RPM, 5000 CFM, and 2 HP, solve by target RPM at 1900 RPM to verify the new power draw stays within the motor's nameplate rating before increasing a belt-drive pulley ratio.
Matching airflow after a filter or coil change increases resistance
If a new, denser filter has changed your system resistance, use the target airflow mode to find what RPM is needed to restore the original CFM, and see the associated increase in power.
Estimating energy savings from a VFD retrofit on a constant-volume fan
Compare a fan currently running at full speed (1800 RPM, 2 HP) against a VFD-trimmed speed of 1400 RPM to estimate the cube-law power savings achievable by slowing the fan instead of using a damper to throttle flow.
Scaling a bench test fan curve to a different RPM point
Given manufacturer test data at 1000 RPM, use the target RPM mode to predict airflow and pressure at the actual operating speed your system will run, without re-testing the fan.
Quick reference
Fan affinity laws — flow, static pressure and power as % of the original operating point
| Fan speed (% of original RPM) | Airflow (CFM) | Static pressure | Fan power |
|---|---|---|---|
| 50% | 50% | 25% | 12.5% |
| 60% | 60% | 36% | 21.6% |
| 70% | 70% | 49% | 34.3% |
| 75% | 75% | 56.3% | 42.2% |
| 80% | 80% | 64% | 51.2% |
| 85% | 85% | 72.2% | 61.4% |
| 90% | 90% | 81% | 72.9% |
| 95% | 95% | 90.3% | 85.7% |
| 100% | 100% | 100% | 100% |
| 105% | 105% | 110.3% | 115.8% |
| 110% | 110% | 121% | 133.1% |
| 120% | 120% | 144% | 172.8% |
| 125% | 125% | 156.3% | 195.3% |
| 150% | 150% | 225% | 337.5% |
| 200% | 200% | 400% | 800% |
Frequently asked questions
What are the fan laws?
For the same fan system, when speed changes, airflow scales linearly with speed, pressure scales with the square of speed, and power scales with the cube of speed.
Can I calculate without knowing pressure or power?
Yes. Pressure and power are optional — leave them blank and only airflow and speed will be calculated.
Does this hold true in every situation?
The fan laws assume the system resistance characteristic (like the ductwork) doesn't change. If duct or damper conditions change, actual values will differ.
Should I solve by target RPM or target airflow?
Use target RPM if you're targeting a specific speed (like a VFD setpoint), or target airflow if you're targeting a specific CFM.
Why does power scale with the cube of speed while airflow only scales linearly?
This comes from basic fan physics: airflow (CFM) is directly proportional to how fast the blades move, pressure rises with the square of speed because kinetic energy scales with velocity squared, and power is the product of pressure and airflow, so it compounds into a cubic relationship. This cube-law relationship is exactly why even modest speed reductions via a VFD can produce large energy savings compared to throttling with a damper at full speed.
Why would I use a VFD instead of a damper to reduce airflow?
A damper restricts flow but the fan motor still spins at full speed, wasting energy as heat and turbulence. A VFD actually slows the fan down, and because power drops with the cube of speed, even a 20% speed reduction can cut power consumption by roughly 50%, making VFDs far more energy-efficient for variable-load applications.
Can I use this for pumps as well as fans?
The same affinity laws apply to centrifugal pumps (flow scales linearly with speed, head with the square, and power with the cube), but this calculator's defaults and terminology (CFM, static pressure) are tailored to air-handling fans. The underlying math works the same way for liquid pumps if you substitute flow rate and head.
Why did my actual measured values not match the calculator's prediction?
Real fans deviate from the idealized affinity laws at the extremes of their operating range, and motor efficiency itself can change with speed (especially below roughly 20-30% of rated speed). Belt slippage, bearing friction, and changes in air density or temperature can also cause small real-world deviations from the theoretical cube and square relationships.
What's the difference between static pressure and total pressure here?
This calculator's pressure field is intended for static pressure, the resistance the fan works against from ductwork, filters, and coils, which is what's typically measured and specified on HVAC equipment and balancing reports. The fan laws apply equally to total pressure, but mixing the two types within one calculation will give inconsistent results.