Duct Size Calculator

Size round or rectangular HVAC ductwork from airflow (CFM) and target air velocity, including equivalent diameter calculations for converting between duct shapes. Free online tool for sizing supply runs, bathroom exhaust branches, or fitting ductwork into a soffit, computed instantly in your browser.

Duct shape
Target velocity

1,200 FPM (6.1 m/s)

Result

Duct diameter

12.36 in

313.96 mm

Airflow

1,699.01 m³/h

Usage examples

Finding a round duct diameter for a given airflow

Enter the required airflow (CFM) and a target velocity to get the appropriate round duct diameter right away.

Sizing a rectangular duct to fit a ceiling space

When one side of a rectangular duct is constrained, calculate the other side needed to meet the required airflow.

Designing quickly with typical velocities by section

Pick a typical recommended velocity for supply mains, branches, or return ducts to speed up design work.

Converting an existing round duct run to rectangular for a soffit

A 14-inch round duct carrying 1,600 CFM needs to fit inside an 8-inch-deep soffit. Switch to rectangular, enter 8 in as one side, and solve for the other side needed at the same target velocity, then compare the resulting equivalent diameter back against the original 14-inch round size.

Sizing a bathroom exhaust branch at low airflow

For a 2,000 CFM supply main feeding several branches, size an individual 80 CFM bathroom exhaust branch using the return/exhaust velocity preset to confirm a small round duct size is adequate without excessive noise from oversized velocity.

Comparing equivalent diameter for two different aspect ratios

For the same 1,200 CFM airflow, compare a 24 in x 8 in rectangular duct against a 16 in x 12 in rectangular duct to see how a flatter aspect ratio increases the equivalent diameter and friction loss even though both have the same face area.

Quick reference

Round duct diameter (in) by airflow and velocity

Airflow (CFM)Supply main (1200 FPM)Supply branch (900 FPM)Return (800 FPM)
50 CFM2.8 in3.2 in3.4 in
100 CFM3.9 in4.5 in4.8 in
150 CFM4.8 in5.5 in5.9 in
200 CFM5.5 in6.4 in6.8 in
250 CFM6.2 in7.1 in7.6 in
300 CFM6.8 in7.8 in8.3 in
400 CFM7.8 in9 in9.6 in
500 CFM8.7 in10.1 in10.7 in
600 CFM9.6 in11.1 in11.7 in
800 CFM11.1 in12.8 in13.5 in
1,000 CFM12.4 in14.3 in15.1 in
1,200 CFM13.5 in15.6 in16.6 in
1,500 CFM15.1 in17.5 in18.5 in
2,000 CFM17.5 in20.2 in21.4 in
2,500 CFM19.5 in22.6 in23.9 in
3,000 CFM21.4 in24.7 in26.2 in

Rectangular duct width (in) for an 8 in duct height

Airflow (CFM)Supply main (1200 FPM)Supply branch (900 FPM)Return (800 FPM)
50 CFM8 × 0.8 in8 × 1 in8 × 1.1 in
100 CFM8 × 1.5 in8 × 2 in8 × 2.3 in
150 CFM8 × 2.3 in8 × 3 in8 × 3.4 in
200 CFM8 × 3 in8 × 4 in8 × 4.5 in
250 CFM8 × 3.8 in8 × 5 in8 × 5.6 in
300 CFM8 × 4.5 in8 × 6 in8 × 6.8 in
400 CFM8 × 6 in8 × 8 in8 × 9 in
500 CFM8 × 7.5 in8 × 10 in8 × 11.3 in
600 CFM8 × 9 in8 × 12 in8 × 13.5 in
800 CFM8 × 12 in8 × 16 in8 × 18 in
1,000 CFM8 × 15 in8 × 20 in8 × 22.5 in
1,200 CFM8 × 18 in8 × 24 in8 × 27 in
1,500 CFM8 × 22.5 in8 × 30 in8 × 33.8 in
2,000 CFM8 × 30 in8 × 40 in8 × 45 in
2,500 CFM8 × 37.5 in8 × 50 in8 × 56.3 in
3,000 CFM8 × 45 in8 × 60 in8 × 67.5 in

Frequently asked questions

What are the velocity presets based on?

They reflect typical recommended velocity ranges commonly cited by SMACNA and similar guidelines. Adjust them to match your actual design criteria.

What does equivalent diameter mean?

It's the diameter of a round duct that would have the same friction performance as the rectangular duct, using the standard ASHRAE/SMACNA formula.

Does this only support CFM?

Input is in CFM (ft³/min); the result also shows an m³/h conversion for reference.

Does this account for insulation or duct liner thickness?

No. This calculator computes only the clear air-flow cross-section; any increase in actual outer dimensions from insulation or liner needs to be accounted for separately.

Why do two rectangular ducts with the same cross-sectional area give different equivalent diameters?

Equivalent diameter depends on both area and perimeter (aspect ratio), not just area. A flatter, more elongated rectangle has more wall surface per unit of airflow area, which increases friction, so it needs a larger equivalent diameter than a near-square duct of the same area to deliver the same airflow with similar pressure loss.

Is this an equal-friction or a velocity method calculator?

This tool uses the velocity method — you pick a target velocity (or a typical preset) and it sizes the duct to hit that velocity at your given airflow. It does not perform equal-friction-rate sizing across a full duct system with multiple branches; for that you would size each section while holding friction rate per 100 ft constant, which requires tracking cumulative pressure loss across the whole run.

Why is my duct velocity preset so much higher or lower than what another source recommends?

Recommended velocities vary by application (residential vs. commercial), duct location (main vs. branch vs. final run), and noise tolerance. The presets here reflect generally-cited SMACNA ranges, but a quieter space (like a bedroom or recording studio) often calls for lower velocities than an industrial or mechanical room application.

Can I use this for flexible duct instead of rigid sheet metal?

You can get a sizing estimate, but flexible duct has notably higher friction loss than rigid duct of the same diameter, especially if it isn't pulled fully straight and taut. If most of a run uses flex duct, expect higher actual pressure drop than this calculator's clear-airflow sizing alone would suggest.