Refrigerant P-T Chart Calculator

Look up saturation pressure or temperature for common refrigerants including R-410A, R-22, R-134a, and R-404A, with results in psig or bar. Free online pressure-temperature chart for checking refrigerant charge or calculating superheat and subcooling in the field, right in your browser.

Refrigerant
Direction
Temperature unit
Pressure unit

Result

118.8 psig

Usage examples

Checking refrigerant charge

Look up the saturation temperature for a pressure reading off your service port gauge to quickly check whether the system is operating in a normal range.

Getting ready to calculate superheat or subcooling

Find the saturation pressure matching the measured temperature on the suction or liquid line to use as a baseline for superheat or subcooling calculations.

Quickly estimating in the field without a gauge

Even with just a measured pipe surface temperature, estimate the expected saturation pressure for that refrigerant right away.

Diagnosing an R-22 system reading low suction pressure

An older R-22 system reads 48.4 psig on the low side. Look up the corresponding saturation temperature to see it should be around 0°F, then compare that against the actual suction line temperature to judge whether the system is low on charge or has a restriction.

Converting an R-134a manifold reading from psig to bar

A technician in a region using bar-scale gauges needs to cross-check a 6.5 psig R-134a reading. Switch the pressure unit to bar to confirm the equivalent reading and corresponding saturation temperature without manual unit conversion.

Comparing R-410A and R-404A condensing pressure at the same outdoor temperature

At a 100°F outdoor ambient (a common summer high-side design condition), compare the expected condensing pressure for R-410A against R-404A to understand why equipment and gauge sets rated for one refrigerant aren't safely interchangeable with the other.

Quick reference

Saturation pressure (psig) by temperature — R-404A shown as the bubble/dew average

°F°CR-410A (psig)R-22 (psig)R-134a (psig)R-404A (psig)
-40-4010.80.6-7.34.6
-35-37.214.02.6-6.27.0
-30-34.417.64.8-4.99.8
-25-31.721.77.3-3.512.9
-20-28.926.310.2-1.816.4
-15-26.131.013.1-0.119.9
-10-23.336.216.31.823.9
-5-20.642.020.04.028.3
0-17.848.424.06.533.2
5-1554.928.19.038.0
10-12.262.132.611.843.4
15-9.470.037.614.949.4
20-6.778.743.118.456.0
25-3.987.448.621.962.5
30-1.197.054.725.969.7
351.7107.461.330.277.6
404.4118.868.635.086.1
457.2130.275.839.894.7
5010142.683.745.2104.0
5512.8156.192.351.0114.1
6015.6170.7101.657.4125.1
6518.3185.3110.963.8136.1
7021.1201.1121.070.8147.9
7523.9218.1131.978.4160.6
8026.7236.5143.686.7174.4
8529.4254.9155.395.0188.2
9032.2274.6167.9104.0202.9
9535295.8181.4113.7218.7
10037.8318.5195.9124.2235.7
10540.6341.3210.4134.7252.7
11043.3365.6225.8146.0270.9
11546.1391.6242.3158.1290.3
12048.9419.4260.0171.2311.0
12551.7447.4277.6184.3331.8
13054.4477.1296.3198.2354.0
13557.2508.8316.2213.2377.6
14060542.5337.4229.2402.7

Frequently asked questions

Where does this data come from?

It's based on a saturation pressure table computed with CoolProp (an open-source thermodynamic properties library), cross-checked against two independent sources. Intermediate temperatures not in the table are computed via log-linear interpolation.

Why only R-410A, R-22, R-134a, and R-404A?

Only refrigerants with reliably cross-verifiable data are included. We chose a narrower scope over showing unverified numbers.

Why are the R-404A values approximate?

R-404A is a zeotropic blend, so its liquid (bubble point) and vapor (dew point) pressures differ slightly. This tool uses the average of the two to keep things simple — for precise superheat/subcooling work, consult a dedicated glide table.

Can I look up values below -40°F or above 140°F?

Currently only -40°F to 140°F (about -40°C to 60°C) is supported, which covers the range most commonly needed in everyday HVAC/refrigeration field work.

What's the difference between the gauge pressure shown here and absolute pressure?

This tool's psig results are gauge pressure — measured relative to atmospheric pressure, which is what a standard refrigeration manifold gauge reads. Internally, calculations are done in absolute pressure (psia) by adding standard atmospheric pressure (14.696 psi), then converted back to gauge for display, since gauge is what matches field instruments.

Why does R-22 show a positive pressure even in cold temperatures, while some other refrigerants read negative (vacuum) at the same temperature?

Each refrigerant has its own distinct vapor pressure curve based on its molecular properties. At a given temperature, lower-pressure refrigerants like R-134a can sit below atmospheric pressure (showing a vacuum reading in inHg rather than psig), while higher-pressure refrigerants like R-410A stay well above atmospheric even at low temperatures. This is inherent to each refrigerant and not a sign of a problem.

Can I use this P-T chart to directly calculate superheat or subcooling?

This tool gives you one half of the calculation — the saturation temperature or pressure. For superheat, subtract the saturation temperature (from your suction pressure reading) from the actual measured suction line temperature. For subcooling, subtract the actual measured liquid line temperature from the saturation temperature (from your high-side pressure reading). You still need to take the actual line temperature measurement yourself.

Is it safe to use these values for refrigerants not listed, like R-32 or R-454B?

No. Each refrigerant blend has its own unique pressure-temperature relationship, and substituting a similar-sounding refrigerant's data can lead to significant charge or diagnostic errors. Use a P-T chart or tool specific to the exact refrigerant in the system.