Wire Gauge Ampacity Calculator

Look up NEC-style safe current capacity (ampacity) for copper wire by AWG size, factoring in insulation temperature rating. Free online reference for sizing branch circuits, extension cords, sub-panel feeders, and 12V DC runs without installing anything.

Insulation temperature rating

Ampacity

25 A

Covers copper conductors from 14 AWG to 4/0 AWG only, using NEC Table 310.16-style base ampacity values (30°C ambient, no more than 3 current-carrying conductors, no additional derating applied). Aluminum conductors have meaningfully lower ampacity at the same gauge and are not covered here — see the FAQ below.

Usage examples

Checking a residential branch circuit's wire size

Quickly look up a wire gauge suitable for a 20A circuit breaker against the NEC base table.

Sizing an extension cord or low-voltage run

Use the expected load current to pick a wire gauge with adequate headroom.

Comparing insulation temperature ratings

See how much ampacity the same wire gauge gains at a 90°C insulation rating versus 60°C.

Sizing conductors for a sub-panel feeder

Check whether 4 AWG copper at a 75°C insulation rating (85A) has enough headroom for a feeder circuit's expected load before consulting an electrician.

Choosing wire for a car audio or 12V DC power run

Look up the ampacity of 8 AWG or 6 AWG copper to judge whether it's oversized or undersized for a high-current 12V accessory run (note this table is for NEC-style building wiring, not automotive derating standards).

Picking a gauge for a workshop sub-circuit

Compare 12 AWG (25A at 75°C) against 10 AWG (35A at 75°C) when planning a circuit for benchtop power tools.

Quick reference

Copper conductor ampacity (A), 30°C ambient, ≤3 current-carrying conductors, no derating

AWG size60°C75°C90°C
14 AWG15 A20 A25 A
12 AWG20 A25 A30 A
10 AWG30 A35 A40 A
8 AWG40 A50 A55 A
6 AWG55 A65 A75 A
4 AWG70 A85 A95 A
3 AWG85 A100 A110 A
2 AWG95 A115 A130 A
1 AWG110 A130 A145 A
1/0 AWG125 A150 A170 A
2/0 AWG145 A175 A195 A
3/0 AWG165 A200 A225 A
4/0 AWG195 A230 A260 A

Frequently asked questions

Can I use this directly for a real wiring installation?

This shows the NEC base ampacity table value, assuming 30°C ambient and no more than 3 current-carrying conductors. Real installations often need further derating for higher ambient temperatures or more bundled conductors, and must be verified by a qualified electrician against the full code — this tool is for quick reference, not a code-compliant installation calculation.

Does this support aluminum conductors?

No. Aluminum has meaningfully lower ampacity than copper at the same AWG size, and we didn't have confidence in a fully accurate aluminum table, so it's deliberately out of scope. Check NEC Table 310.16's aluminum column directly for that.

What happens if I pick a gauge outside the supported range?

The tool shows an out-of-range message instead of a guessed number. We'd rather narrow the range than show a value we're not confident in.

Why does ampacity increase with a higher temperature rating for the same gauge?

The temperature rating (60°C/75°C/90°C) describes how much heat the conductor's insulation can safely tolerate before it degrades. Higher-rated insulation allows the conductor to run hotter, so it can carry more current before reaching its thermal limit — the copper itself is identical.

Why would I need to derate below the table value?

The base table assumes 30°C ambient air and no more than 3 current-carrying conductors in a raceway or cable. Running wires in a hot attic, bundling many circuits together, or exceeding 3 conductors all trap heat and require a derating factor applied to the base ampacity — consult NEC Table 310.15(B) and the adjustment factors for conductor bundling.

Should I size a wire for the breaker rating or the actual load current?

The conductor ampacity must be at least equal to the breaker/fuse rating protecting it (with some exceptions), and the breaker rating itself should be sized to the actual expected load, not exceed what the wire can safely carry. Undersized wire on an oversized breaker is a fire hazard because the breaker won't trip before the wire overheats.

Does wire length matter for ampacity?

Not for ampacity (heat limit) directly, but long runs suffer voltage drop, which is a separate consideration. A wire can be rated to safely carry a given current over any length, but for long runs you may need a larger gauge than the ampacity table requires just to keep voltage drop within an acceptable percentage.