Pipe Pressure Drop Calculator
Calculate friction head loss in a pipe from flow rate, diameter, length, and pipe roughness, covering both laminar and turbulent flow regimes. Useful for pump selection, comparing pipe materials, or sizing chilled water and glycol loops, with instant results and no sign-up required.
Result
Pressure drop
0.3727 bar
5.4055 psi
Head loss
3.8081 m
Velocity
2 m/s
Reynolds number
199,201.5968
Flow regime
Turbulent
Usage examples
Checking pressure drop for pump selection
Enter your target flow rate and pipe specs to calculate the friction-caused pressure drop, then use it to pick an appropriately-rated pump.
Comparing loss across pipe materials
See how pressure drop changes with pipe material (roughness) for the same flow rate.
Checking laminar vs. turbulent flow
Compute the Reynolds number to see whether your conditions are laminar or turbulent, and how adjusting velocity changes that.
Sizing a chilled water branch line at 2 m/s
For a 65 mm copper branch line carrying chilled water at a target velocity of 2 m/s over a 45 m run, switch to velocity input mode to get the pressure drop and Reynolds number without first converting to a flow rate.
Evaluating an old galvanized domestic water riser
For a 25 mm galvanized steel riser carrying 40 L/min over 30 m of vertical run, compare the pressure drop against the same line modeled as new copper to see how much scale buildup and material choice affect head loss over the riser's life.
Sizing a glycol loop with custom fluid properties
For a 50/50 propylene glycol mix at roughly 1040 kg/m³ and 0.0025 Pa·s viscosity running through 80 mm PVC pipe at 300 L/min over 60 m, use the custom fluid option since glycol's higher viscosity meaningfully changes the Reynolds number and pressure drop versus plain water.
Quick reference
Commercial steel — pressure drop (kPa) per 100 m of pipe, water at 20 °C
| Inner diameter (mm) | 0.5 m/s | 1 m/s | 1.5 m/s | 2 m/s | 2.5 m/s | 3 m/s |
|---|---|---|---|---|---|---|
| 15 mm | 31.5 kPa | 110.7 kPa | 235.1 kPa | 403.9 kPa | 616.9 kPa | 874 kPa |
| 20 mm | 21.6 kPa | 76.3 kPa | 162.3 kPa | 279.1 kPa | 426.5 kPa | 604.5 kPa |
| 25 mm | 16.2 kPa | 57.3 kPa | 122.1 kPa | 210 kPa | 321.1 kPa | 455.2 kPa |
| 32 mm | 11.8 kPa | 41.9 kPa | 89.2 kPa | 153.7 kPa | 235 kPa | 333.2 kPa |
| 40 mm | 8.9 kPa | 31.6 kPa | 67.4 kPa | 116.1 kPa | 177.6 kPa | 251.8 kPa |
| 50 mm | 6.7 kPa | 23.9 kPa | 50.9 kPa | 87.8 kPa | 134.4 kPa | 190.6 kPa |
| 65 mm | 4.8 kPa | 17.2 kPa | 36.8 kPa | 63.4 kPa | 97 kPa | 137.7 kPa |
| 80 mm | 3.7 kPa | 13.3 kPa | 28.4 kPa | 49 kPa | 75.1 kPa | 106.6 kPa |
| 100 mm | 2.8 kPa | 10.1 kPa | 21.6 kPa | 37.3 kPa | 57.1 kPa | 81 kPa |
| 125 mm | 2.1 kPa | 7.7 kPa | 16.4 kPa | 28.4 kPa | 43.5 kPa | 61.7 kPa |
| 150 mm | 1.7 kPa | 6.1 kPa | 13.1 kPa | 22.7 kPa | 34.8 kPa | 49.4 kPa |
| 200 mm | 1.2 kPa | 4.3 kPa | 9.3 kPa | 16 kPa | 24.6 kPa | 34.9 kPa |
| 250 mm | 0.9 kPa | 3.3 kPa | 7.1 kPa | 12.2 kPa | 18.8 kPa | 26.6 kPa |
| 300 mm | 0.7 kPa | 2.6 kPa | 5.7 kPa | 9.8 kPa | 15.1 kPa | 21.4 kPa |
PVC — pressure drop (kPa) per 100 m of pipe, water at 20 °C
| Inner diameter (mm) | 0.5 m/s | 1 m/s | 1.5 m/s | 2 m/s | 2.5 m/s | 3 m/s |
|---|---|---|---|---|---|---|
| 15 mm | 28.1 kPa | 93.2 kPa | 189.8 kPa | 315.4 kPa | 468.7 kPa | 648.6 kPa |
| 20 mm | 19.4 kPa | 64.9 kPa | 132.6 kPa | 220.9 kPa | 328.8 kPa | 455.6 kPa |
| 25 mm | 14.6 kPa | 49.1 kPa | 100.6 kPa | 167.9 kPa | 250.1 kPa | 346.9 kPa |
| 32 mm | 10.7 kPa | 36.2 kPa | 74.2 kPa | 124.1 kPa | 185.1 kPa | 256.9 kPa |
| 40 mm | 8.1 kPa | 27.4 kPa | 56.5 kPa | 94.5 kPa | 141.2 kPa | 196.1 kPa |
| 50 mm | 6.1 kPa | 20.9 kPa | 43 kPa | 72.1 kPa | 107.8 kPa | 149.9 kPa |
| 65 mm | 4.4 kPa | 15.1 kPa | 31.3 kPa | 52.5 kPa | 78.6 kPa | 109.4 kPa |
| 80 mm | 3.4 kPa | 11.8 kPa | 24.3 kPa | 40.9 kPa | 61.3 kPa | 85.3 kPa |
| 100 mm | 2.6 kPa | 9 kPa | 18.6 kPa | 31.3 kPa | 46.9 kPa | 65.4 kPa |
| 125 mm | 2 kPa | 6.8 kPa | 14.2 kPa | 24 kPa | 36 kPa | 50.2 kPa |
| 150 mm | 1.6 kPa | 5.5 kPa | 11.4 kPa | 19.3 kPa | 29 kPa | 40.4 kPa |
| 200 mm | 1.1 kPa | 3.9 kPa | 8.1 kPa | 13.7 kPa | 20.6 kPa | 28.8 kPa |
| 250 mm | 0.9 kPa | 3 kPa | 6.2 kPa | 10.5 kPa | 15.8 kPa | 22.1 kPa |
| 300 mm | 0.7 kPa | 2.4 kPa | 5 kPa | 8.5 kPa | 12.8 kPa | 17.9 kPa |
Frequently asked questions
What formula does this use?
The Darcy-Weisbach equation, with the friction factor computed via the Swamee-Jain approximation, which avoids the iterative solving the classic Colebrook-White equation requires.
Can I calculate for fluids other than water?
Yes. Choose 'Custom' to enter density and viscosity directly for other fluids, like oil.
How is the roughness value chosen?
Selecting a pipe material applies a commonly-used absolute roughness value automatically. For materials with wide variance, like concrete, actual values can differ based on real-world condition.
Can I use this result directly for a real design?
This calculator only accounts for straight-pipe friction loss, not minor losses from valves and fittings. A real design needs to account for those additional losses too.
Why does switching between flow rate and velocity input give slightly different results for the 'same' condition?
They shouldn't differ for truly matching conditions — but if you enter a flow rate in one mode and later estimate velocity by hand for the other mode, small rounding in that conversion can shift the result. For exact comparisons, use flow rate mode and let the tool derive velocity rather than entering an independently rounded velocity value.
What does the flow regime (laminar vs. turbulent) actually affect?
It determines which friction factor formula applies. Below a Reynolds number of about 2300, flow is laminar and friction factor is calculated as 64/Re; above that, this tool uses the Swamee-Jain turbulent approximation. Most real-world water and air distribution piping runs turbulent — laminar flow is typically only seen with highly viscous fluids or very low velocities.
Why is my calculated pressure drop so much higher than what a manufacturer's chart shows for the same pipe?
Manufacturer charts sometimes assume a different reference temperature, a different roughness value for 'new' versus 'aged' pipe, or already include a typical allowance for fittings. Check what assumptions the chart states and compare them against the material and fluid properties used here.
Does pipe diameter mean nominal size or actual inner diameter?
Enter the actual inner diameter, not the nominal trade size. For example, a 'nominal' 4-inch steel pipe has an inner diameter that varies by schedule (wall thickness), so look up the actual ID for your specific pipe schedule rather than using the nominal label directly.